EAN kod8595057632592
Tarifni broj83024190
Težina0,3709 kg/pcs
Površinska obradaHot Dip Galvanized
Funkcionalnost u požaruP90-R, E90, PS90
Standardi otpornosti na vatruČSN 73 0895, DIN 4102-12, STN 92 0205
Maksimalno opterećenje230 kg
Dimenzija A170 mm
Dimenzija B120 mm
Dimenzija C60 mm
Za širinu kabelske ploče150 mm
Za visinu kabelske police35 - 110 mm
Maks. opterećenje za vatrootpornost10 - 20 kg

The holder is designed to be mounted on a wall or a ceiling profile. For assembly to the ceiling profile SPL and SPS there are used the sliding nuts PM 41 M 10 together with the bolts S 10X20 (2 pcs). Fix to the celling profile SPLN, SPSN or SPU using bolts S 10X20, nuts M 10 and washer PD 10. Cable tray attaching to the bracket DT is carried out by bolts NSM 6X10.

Note for system with maintained functionality in fire:
You find more information in the catalogue Systems with maintained functionality in fire.