EAN kod | 8595568932358 |
Tarifni broj | 39259080 |
Težina | 0,0620 kg/pcs |
Boja | black + gray |
Materijal | PP |
Bezhalogeni materijal | yes |
Materijal bez ulja | yes |
Zvučna izolacija | yes |
Samogasivi | 30 s |
Nazivni napon | <= 400 V |
Nazivna struja | <= 16 A |
Otpornost na temperaturu | -5 - 60 °C |
Probna petlja | 850 °C |
Način montaže horizontally max. 3 pieces of boxes next to each other, vertically max. 2 pieces next to each other | |
Širina | 73 mm |
Visina | 65 mm |
Dubina | 47 mm |
Promjer rupa (bušenih) | 73 mm |
Preporuka proizvođača For all range of products in hollow walls, we recommend using the milling sets supplied by us. | |
Klasa reakcije na požar podložnog materijala | A1 - F |
Omogućava montažu dvostruke utičnice | yes |
Vrste zaštite | IP 30 |
Standardi ČSN EN 60 670-1, ČSN EN 1363-1:2013, ČSN 73 08 10 | |
Standardi otpornosti na vatru | EI 15 - EI 120 |
Opis paketa the box is fitted with screws for fixing onto plasterboard and with instrument screws, pack loosely in a box |
Wiring device box for fire partitions. Suitable for installation in plasterboard and aerated concrete structures. Designed for distribution with voltage up to 400 V. Inlet openings made of flexible material. Ensured airtightness of the passage even when the cable or pipe is inserted. Foaming material on the outside and inside of the box. In the event of a fire, this material quickly changes its volume (swells) and thus seals the installation opening of the box and prevents the passage of fire through the partition. The IP30 protection a box fitted with an appropriate lid or a device with a higher or equal IP30 protection. The diameter of the installation hole is 73 mm. Mounting screws and metal feets are provided with a three-way thread for quick installation. Suitable for buildings with increased personal and property protection in case of fire. The box is available in selected countries.
Note for system with maintained functionality in fire:
Fire integrity and insulation up to 120 minutes (EI 15 - EI 120). The fire protection material inside and outside the box.
The PO classification is dependent on the specific placement of the box in plasterboard or aerated concrete, detailed in the new catalog – Systems with maintained functionality in fire.